Skip to content
DCIM Professionals DCIM Professionals

Electrical Planning Reference

Circuit Load Reference Chart

Practical planning guidance for circuit load, current draw, breaker utilization, power factor and voltage drop. Use this page as a reference, then use the calculator for exact project inputs.

Core formulas

The formulas below are planning formulas for balanced loads. They do not replace full electrical design.

Single phase current: A = W ÷ (V × PF)
Three phase current: A = W ÷ (√3 × V × PF)
Utilization: % = load current ÷ breaker rating × 100
Voltage drop: based on current, conductor resistance, cable length and cross-section

Common breaker sizes

These are common planning values only. Available protective devices and permitted use depend on local standards, installation rules, cable type and site design.

6 A10 A13 A16 A20 A25 A32 A40 A50 A63 A80 A100 A125 A160 A200 A250 A

Utilization guidance

Utilization should be checked against the project rules, continuous-load requirements, protection device, cable rating and operating conditions.

Utilization Status Planning note
≤ 50% Comfortable planning zone Good headroom if the circuit, cable and protection design are otherwise correct.
50–80% Normal monitored zone Common practical planning range for many continuous-load assumptions.
80–100% Warning zone Check continuous-load rules, cable sizing, installation conditions and future growth.
> 100% Over rating The calculated load exceeds the selected breaker rating. Redesign is required.

Conductor planning notes

Cross-section selection depends on much more than current alone. Installation method, grouping, ambient temperature, insulation type, route length and protection device all matter.

Cross-section Planning note
1.5 mm² Often used for light circuits, but final current capacity depends heavily on installation method and local rules.
2.5 mm² Common for many socket/outlet circuits, subject to protection, installation method and derating.
4–6 mm² Often used where longer routes, higher load or lower voltage drop are required.
10 mm²+ Used for higher-current feeders or longer routes, always requiring proper design verification.

How to use this reference

Identify the electrical system: single-phase or three-phase.

Enter the expected active power in watts.

Use an appropriate power factor for the load.

Calculate expected current draw.

Compare current draw against breaker rating and safe utilization target.

Check voltage drop for cable length, conductor material and cross-section.

Verify final design against qualified electrical review and local standards.

Common mistakes

Treating breaker rating as continuous usable capacity without headroom.

Ignoring power factor for real equipment loads.

Using three-phase formulas for single-phase loads, or the other way around.

Ignoring voltage drop on longer cable runs.

Assuming cable cross-section alone determines compliance.

Forgetting installation method, ambient temperature and grouping derating.

Voltage drop notes

Voltage drop becomes more important with longer cable runs, higher current and smaller conductor cross-sections. A low current circuit may pass easily, while a high current circuit on a long route may need a larger conductor.

Always verify acceptable voltage drop against project requirements and applicable standards.

Worked example

A 2,800 W continuous load is planned on a 230 V single-phase circuit with a 0.95 power factor.

Power 2,800 W
Estimated current ≈ 12.8 A
16 A utilization ≈ 80%

This may be acceptable as an early estimate, but final approval still depends on the protective device, cable sizing, installation method, voltage drop and local rules.

FAQ

Can this replace electrical design?

No. This is a planning reference only. Final circuit design must be verified by qualified electrical review and applicable local rules.

Why include power factor?

Many real electrical loads do not behave as perfect resistive loads. Power factor affects the current required to deliver the same active power.

Why check voltage drop?

Long cable runs and high current can create excessive voltage drop even when breaker utilization looks acceptable.

Next step

Need the exact result?

Use the Circuit Load Calculator to enter voltage, power, breaker rating, power factor, conductor material, cable cross-section and route length.

Open calculator →

Disclaimer

This reference chart provides planning guidance only. It does not replace qualified electrical design, local regulations, IEC/VDE/NEC requirements, circuit protection review, conductor sizing, derating, manufacturer documentation, site standards or professional inspection.