Skip to content
DCIM ProfessionalsDCIM Professionals

Electrical Tool

kVA / kW / Amps Converter

Convert between apparent power (kVA), real power (kW) and current for single-phase and three-phase systems using voltage and power factor.

Updated: June 29, 2026Planning reference

Quick Answer

Convert kVA, kW and amps for any single- or three-phase circuit.

Pick the value you know (kVA, kW or amps), set the phase, voltage and power factor, and the calculator returns current, apparent power, real power and reactive power. Three-phase uses the √3 line-to-line relationship.

Power Conversion

Input values

Use the line-to-line voltage for three-phase systems. Power factor (cos φ) links real power to apparent power; use 1.0 for resistive loads and ~0.8–0.95 for typical motor or IT loads.

System

Value

Formula basis

Single-phase: kVA = V × A ÷ 1000. Three-phase: kVA = √3 × V × A ÷ 1000. Real power kW = kVA × PF, and reactive power kVAR = √(kVA² − kW²).

Formula / Method

What the calculator does

From the value you know, the calculator derives apparent power (kVA), then applies power factor to get real power (kW) and the Pythagorean relationship to get reactive power (kVAR). Current follows from the phase and voltage relationship.

kW = kVA × PF · kVAR = √(kVA² − kW²)

Inputs

Required inputs

Use phase (1Ø/3Ø), line-to-line voltage, power factor and one known quantity — apparent power, real power or current. The other quantities are calculated.

Uses

Where this helps

Useful for sizing breakers, cables, generators and UPS, reading nameplate data, and converting between equipment ratings given in kVA, kW or amps.

FAQ

Power conversion notes

What is the difference between kVA and kW?

kVA is apparent power — the total the supply must deliver. kW is real power that does useful work. They are linked by power factor: kW = kVA × PF. At PF 1.0 they are equal; at lower PF the kVA is higher than the kW for the same useful output.

Why is three-phase different?

Three-phase power uses the line-to-line voltage and a √3 factor: kVA = √3 × V × A ÷ 1000. For the same power, three-phase draws less current per conductor than single-phase, which is why it is used for larger loads.

What power factor should I use?

Use 1.0 for purely resistive loads (heaters, incandescent lighting), ~0.95 for modern IT/PSU loads, 0.8–0.9 for motors, and the nameplate value when known. UPS and generator ratings are often quoted at 0.8 or 0.9 PF.

Project

Need help with power sizing or electrical design?

ITCOREOPS can support load and power sizing, UPS and generator selection, rack power planning, structured cabling, documentation and operational handover.

Disclaimer

Planning reference only

This calculator provides a simplified conversion for planning only. It does not replace qualified electrical design, NEC/IEC review, nameplate data, harmonic or unbalanced-load analysis, or professional inspection. Verify power factor and voltage against the actual installation.

Workflow

Convert nameplate ratings before sizing breakers, cables, UPS or generators.

Use this converter to translate equipment ratings between kVA, kW and amps so your protection and conductor sizing use consistent units.

Use exact inputs ↑

Support

Need help with electrical or infrastructure planning?

For power sizing, rack power, UPS, structured cabling and operational infrastructure support, visit ITCOREOPS.

Feedback

Found a bug or result issue?

Report display problems, calculation issues or suggestions for improving this calculator.

Worked example

Inputs: 100 kVA at power factor 0.9, 400 V three-phase.

Result: kW = 100 × 0.9 = 90 kW; I = 100 000 ÷ (√3 × 400) ≈ 144 A.